Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM06175
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/11/2020 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
| 09/15/2020 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 09/23/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 09/23/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 09/23/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/29/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/02/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 10/19/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A000; Occupant Load: This Table Title indicates Suite 1610, while the Table Calculation indicates 18th Floor Suite 1820 (3152 GSF), and 16th Floor Suite 1820 (553 NSF). Please clarify. 2. Sheet A100 (Keynote 1); Sheet A101 (Detail 4): At the east wall of the new Server Room, Keynote 1 indicates to extend the wall (Wall Type 2) to the deck. Detail 4/A101 (for Wall Type 2) indicates the new wall stopping at the ceiling with new brace angles. Please coordinate. 3. General: Please provide a project valuation (labor + materials). 4. General: Please provide written responses to all review comments. |
| 10/19/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |