Permit Number: T20CM06164
Parcel: 11708220A

Address:
930 S 8TH AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM06164
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/23/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: T20CM06164
930 S 8th Ave
Addition and Interior Remodel
Residential (2nd Review)

TRANSMITTAL DATE: September 24, 2020

This site is located in the R-3 zone (UDC 4.7.12).

COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

Perimeter yard setbacks are based on the highest point of the wall measured to design grade, see UDC Article 6.4.5.B.1 and Figure 6.4.5-A.

1. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 9’-0” the required perimeter yard setback from the proposed addition to the south property line is 6’-0”, proposed perimeter yard setback is 3’-0”.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
12/01/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed