Permit Number: T20CM06164
Parcel: 11708220A

Address:
930 S 8TH AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM06164
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2020 ANDREW CONNOR NPPO REVIEW Passed
09/24/2020 SSHIELD1 ENGINEERING REVIEW Passed
09/24/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: T20CM06164
930 S 8th Ave
Addition and Interior Remodel
Residential (1st Review)

TRANSMITTAL DATE: September 24, 2020

This site is located in the R-3 zone (UDC 4.7.12).

Perimeter yard setbacks are based on the highest point of the wall measured to design grade, see UDC Article 6.4.5.B.1 and Figure 6.4.5-A.

1. Provide a height dimension from the highest point of the wall to design grade for the south and north walls of the proposed structure. A Design Development Option will be required for the south property line perimeter yard setback and possibly for the north property line. Once the heights are provided Zoning will provide the required comments to process the DDO.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
10/06/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM06164
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

1. Indicate the location and size of buildings, utility meters and gas, water, electric and sewer lines from property line to building, R106.1.1.

FLOOR PLANS:

1. New exterior walls (laundry room) with a fire separation distance less than 3-foot require not less than one-hour fire-resistive construction, R302.1 (City of Tucson Amended). Also, the dryer vent may not pass through the wall.
2. Replaced windows located within the 3-foot distance to property line require a one-hour fire-resistive rating, R302.1. These windows may not open. A glass block assembly may be considered.
3. Show porch roof structures with one-hour fire-resistive construction on the underside in compliance with IBC Table 721.1(2), or show a clear 3’ fire separation distance to the property line.

SECTIONS - DETAILS:

1. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806.
2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

PLUMBING PLANS:

1. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Show the line between the meter and first branch tee is 1-1/4” and a 1” between the furnace branch and range.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation, or controlled exhaust with a calculated airflow rate, R303.4; N1103.6 & M1505.4. Show the system and appropriate flow rate setting on the plans. A two or three bedroom dwelling of 1501 – 3000 SF requires a 60 CFM continuous setting.
2. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Notate if the mechanical system calculations may be provided by deferred submittal.
3. Show a transfer grill in the laundry room interior wall or door for providing combustion air space of 50 CU FT for each 1,000 BTU, G2407.5.1.

ELECTRICAL PLANS:

1. Show or notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.

If you have any questions, please contact:
Ken Van Karsen
(520) 791-5550
City of Tucson Residential Plan Review