Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM06148
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/10/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide detailed information including hardware as to how the proposed line side interconnection is to be performed. 2. Provide a grounding detail and module racking system detail showing how the equipment grounding is to be performed. Include hardware that meets NEC and UL requirements. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 09/10/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 09/14/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 09/22/2020 | MALLORY RESS | ZONING | REVIEW | Approved | |
| 09/22/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Passed |