Permit Number: T20CM06148
Parcel: 13014005A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM06148
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide detailed information including hardware as to how the proposed line side interconnection is to be performed.
2. Provide a grounding detail and module racking system detail showing how the equipment grounding is to be performed. Include hardware that meets NEC and UL requirements.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
09/10/2020 LOREN MAKUS ENGINEERING REVIEW Passed
09/14/2020 JPEELDA1 FIRE REVIEW Approved
09/22/2020 MALLORY RESS ZONING REVIEW Approved
09/22/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Passed