Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM06022
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/03/2020 | PC_CANDERS1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. In regards architect's response to previous building review comment 2, the resubmitted drawing set has 14 architectural sheets of which only 9 were revised to add an Arizona registrant's seal. The remaining 5 sheets still bear the seal of a Texas registrant. Resubmit the drawing set with every sheet bearing a State of Arizona professional registrant's seal. 2. In regards to architect's response to previous building review comment 3, the resubmitted structural calculations are also secured and a City of Tucson approval stamp cannot be placed on them. |
| 12/03/2020 | PC_CANDERS1 | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 12/03/2020 | PC_CANDERS1 | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 12/03/2020 | PC_CANDERS1 | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Add air economizer to Rooftop Unit Schedule on sheet M2 for RTU-1 per COMcheck. |