Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM06019
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations and additions.

PLACE each plan sheet into a single PDF file.

Use the Residential Plan Requirements & Checklist at https://www.tucsonaz.gov/pdsd/residential-permits

Sample plans are available on request. PDSD-Residential@tucsonaz.gov

SITE PLAN:

Provide a site plan showing all buildings, R106.1.1. Show setbacks to property lines and location of utility lines to the building.

FLOOR PLAN:

Provide a floor plan showing each room with labeled function. Show both the enclosed patio and the adjacent room with function identified. Scale ¼” = 1’. Label the function of each room. Show door and window size.

SECTIONS - DETAILS:

Provide structural details showing code compliant materials and fasteners from the foundation to the roof covering of new exterior walls. Include the foundation dimensions and floor separation from grade. Show rating of insulation both walls and ceiling. Walls require compliant attachment to a foundation with a minimum 6" spacing above exterior grade.

PLUMBING PLANS:

Provide piping details showing code compliant materials and sizes.

MECHANICAL PLANS:

Provide equipment details showing code compliant components, locations and sizes.

ELECTRICAL PLANS:

Provide wiring details showing code compliant devices and sizes. Show circuit number and size with receptacles at all walls and lighting control at each doorway both interior and exterior.

OUTDOOR LIGHTING CODE:

Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

INTERNATIONAL ENERGY CONSERVATION CODE:

Provide insulation details showing code compliant placement of materials and ratings, N1101. Solar heat gain of 0.25 or better.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
04/26/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T20CM06019
Residential Addition
April 26, 2021
The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.
1. This comment was not fully addressed. Provide a residential plot plan that shows the entire parcel and all of the requirements shown at the link below. Please resubmit the plans conforming to the requirements of the residential plot plan found at the following link: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf
b. This comment was not addressed. Please show the building elevations for the new addition. The height of the addition is unclear.
2. This comment was not addressed correctly. The vehicle parking cannot be in the front yard. For any single-family dwelling in the R-1 zone with five bedrooms, three parking spaces are required. All parking spaces must be located on-site, either in a side or rear perimeter yard. A dustproof parking surface is required to at least a minimum of two inches of compacted pea gravel. (4.9.7.b.7 udc). The increase in bedrooms on the lot requires adherence to the parking standards above. Please show three parking spaces in the side or back yard at 8.5' x 18'.

Please resubmit showing the following:
Building Elevation Drawings
Parking Spaces in the side or rear yard

If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov