Permit Number: T20CM06005
Parcel: 137330140

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM06005
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2020 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: Steve Shields
PDSD Zoning Review

PROJECT: T20CM06005; Patio Addition
Building Plans (2nd Review)
6061 S Birchwood Dr – R-2 Zone

TRANSMITTAL DATE: October 26, 2020
DUE DATE: October 26, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review comments were addressed.

1. Provide a lot coverage calculation on the plot plan.

2. The parcel dimensions are not correct.

3. Provide a legal description on the plot plan, "OAKTREE AT MIDVALE LOT 754".

4. The plot plan shall be drawn at an Engineering scale such as 1" = 10'.

5. Provide the height of the proposed porch on the plot plan.

6. Indicate the zoning of the property and the surrounding properties.

7. Per UDC Table 6.3-2.A the perimeter yard setback for the proposed porch to the north & south property line is six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each property line. For a porch structure the wall height is measured from design grade to where the beams meet the roof joists. Has no height were provide on the plan additional comments may be forth coming once all required information is provided. A Design Development Option (DDO) will be require to reduce the perimeter yard setbacks. DDP application can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf

Residential plot plan requirements can be found at:
:https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf

If you have any questions about this transmittal, please contact me at Elisa.Hamblin@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans
10/26/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Show or notate a 6” minimum separation of untreated exterior posts above finished grade WITH metal pedestal base with 1" space above concrete, R317.1.4 exception 1 OR show pressure treated posts on the plan.