Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM06002
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/02/2021 | JGARCIA1 | BUILDING-COMMERCIAL | REVIEW | Completed | |
09/02/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments also provide a written response. The resubmittal for the exterior lighting calculations was not completely addressed for compliance with the 2012 Tucson/Pima County Outdoor Lighting Code, (OLC). As requested per the previous electrical comments; (a) Indicate the lighting area and option selected in Table 401.1 for calculating the allowed lumen values per acre. (b) The Parcel of the site # 126-21-0350 is recorded per Pima County GIS as 1.62 acres in size not 1.48 as stated in the lumen calculations. The luminaire quantities and identification marks shown on plan sheets ‘LU-2’, ‘LU-3a’, ‘LU-3b', ‘LU-5’, ‘LU-6’ ‘LU-6a’ do not all correlate with the ‘ELECTRICAL LOAD CALCULATION’ table on plan sheet LU-3a. Please clarify. Per the amount estimated proposed total lumens, this project will require a special inspection. Please indicate this with a note on the plan as required per section 104.2.2, 104.2.1. Indicate controls utilized for curfew requirements for un-shielded lighting as required per section 401, 403. Ref; 2018 IBC 107.2.1, 2017 NEC, 2018 IECC, 2012 Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. |