Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM06002
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/09/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 09/14/2020 | SSHIELD1 | OIP | REVIEW | Passed | |
| 09/14/2020 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 09/14/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 10/13/2020 | KROBLES1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/13/2020 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Please respond to all review questions in writing. 2. The basic wind speed is shown in the structural calculations Basic Values as 95.0 mph. However, the 2018 IBC Figure 1609.3(1) indicates that the basic wind speed V for Tucson, Arizona is 105 mph. Please review the calculations and adjust accordingly. 3. Please submit lumen calculations for all exterior light fixtures on this parcel, new and existing, to show conformance with the 2012 City of Tucson/Pima County Outdoor Lighting Code Table 104.1. In that Table select a commercial option and provide total lumens and unshielded lumens calculations in tabular form to prove compliance with allowable total and unshielded lumens for this 1.62 acre site in lighting area E3. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/13/2020 | PC_CANDERS1 | OUT TO CUSTOMER | Reqs Change |
| 10/13/2020 | PC_CANDERS1 | REJECT SHELF | Reqs Change |
| 10/13/2020 | PC_CANDERS1 | APPROVAL SHELF | Reqs Change |