Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM05979
Parcel: 13316020R

Address:
6586 E GRANT RD

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T20CM05979
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2020 ANY COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active
08/31/2020 ANY FIRE REVIEW Active
08/31/2020 ANY BUILDING-COMMERCIAL REVIEW Active
09/11/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/11/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/11/2020 ROBERT SHERRY WATER REVIEW Completed
09/21/2020 DTRAMME1 ENGINEERING REVIEW Passed
09/23/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide receptacles spaced apart in the meeting/conference rooms as required per NEC art 210.71.
2. Revise IECC lighting calculations to the 2018 IECC.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
09/28/2020 STEVE SHIELDS ZONING REVIEW Approved