Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM05958
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/10/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Appliances (e.g. beverage dispensers, ice makers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device required for each water connection. At a minimum, coffee machines and non-carbonated beverage dispensers require the use of a backflow preventer listed to either ASSE 1022, ASSE 1024, or an air gap. Reference: Sections 608.1, 608.3, and 608.17.1.2 IPC 2018. |
09/10/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
09/10/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
09/21/2020 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
09/23/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide receptacles spaced apart in the meeting/conference rooms as required per NEC art 210.71. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
09/28/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
10/06/2020 | MALLORY RESS | ZONING | REVIEW | Approved | |
10/06/2020 | MRESS1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
10/08/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |