Permit Number: T20CM05881
Parcel: 119034250

Address:
507 W 43RD ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM05881
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2020 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Steve Shields
Site Section Manager


PROJECT:
507 W 43rd St
Addition to SFR
T20CM05881

TRANSMITTAL: September 10, 2020
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 12'-6" the required perimeter yard setback to the east property line is 8'-4", proposed setback is 6'-0".

Perimeter yard setbacks are based on the highest point of the wall measured to design grade, see UDC Article 6.4.5.B.1 and Figure 6.4.5-A.

DDO requirements can be found at:
https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf
09/10/2020 SSHIELD1 ENGINEERING REVIEW Passed
09/10/2020 SSHIELD1 NPPO REVIEW Passed
09/29/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed