Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a complete electrical floor plan including designated branch circuits and panel for the proposed electrical work. Include a complete panel schedule with load calculations to verify code compliance with panel loading. Plan must be sealed by a Registered Engineer registered in the State of Arizona.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/13/2020 PCAMARE1 OUT TO CUSTOMER Completed