Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM05861
Parcel: 11012094F

Address:
5301 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM05861
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2020 JPEELDA1 FIRE REVIEW Approved
09/18/2020 STEVE SHIELDS ZONING REVIEW Approved
09/29/2020 SBLOOD1 ENGINEERING REVIEW Reqs Change 1. Spot elevations and finish floor elevation needs to match development package – please update

2. Ensure that any roof drain scuppers are underneath the circulation path and show in response what page in the plans they can be found

Stephen Blood
stephen.blood@tucsonaz.gov
10/07/2020 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Please respond to all review comments in writing.
2. Per 2018 IBC 1008.2.3 illumination shall be provided along the path of travel for the exit discharge from the exit doors to a public way. No exterior lighting is shown in these plans, therefore please show that the exception to this Code Section is satisfied.
10/07/2020 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Please respond to all review comments in writing.
2. South elevations 2/A5.1 shows an evaporative cooler and a wall louver being removed from the existing shop building. Please confirm whether or not this louver must be replaced in the existing building elsewhere, presumably for proper functioning of the evaporative coolers.
3. The new addition requires ventilation per 2018 IMC 401.2. Either show that the proposed openings in exterior walls satisfy the natural ventilation requirements per Section 402 of the 2018 IMC, or provide mechanical ventilation per Section 403.
10/07/2020 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change 1. Please respond to all review comments in writing.
2. Section 0721 Building Insulation, item G, on sheet G3.1 indicates R-19 batt (cavity) insulation for exterior walls. However, details on sheet A10.1 show 2 ½" of rigid insulation only for exterior walls. Prescriptively, Table C402.1.3 of the 2018 IECC requires R-13 cavity insulation plus R-6.5 continuous insulation. Please coordinate the information in these drawings.
3. That note on sheet G3.1 also specifies R-30 batt insulation for the roof. However, details on sheet A10.1 show what appears to be rigid insulation with a note to match the existing shop building roofing system. Please coordinate the information in the Specification with the building details.
4. Per Deferred Submittals note on sheet S0.1, please have the structural engineer review the metal building drawings and calculations and place his review seal on them.
5. Submit Varco Pruden metal building structural calculations that are not secured so that the City of Tucson approval stamp can be applied and file flattened.
10/07/2020 PIMA COUNTY WATER REVIEW Passed
10/07/2020 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Please respond to all review comments in writing.
2. Provide roof drainage gutter and drain calculations per 2018 IPC Chapter 11.
12/02/2020 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2020 JGARCIA1 APPROVAL SHELF Completed
12/02/2020 JGARCIA1 OUT TO CUSTOMER Completed
12/02/2020 JGARCIA1 REJECT SHELF Completed