Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM05861
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/17/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
09/18/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
09/29/2020 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | 1. Spot elevations and finish floor elevation needs to match development package – please update 2. Ensure that any roof drain scuppers are underneath the circulation path and show in response what page in the plans they can be found Stephen Blood stephen.blood@tucsonaz.gov |
10/07/2020 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Please respond to all review comments in writing. 2. Per 2018 IBC 1008.2.3 illumination shall be provided along the path of travel for the exit discharge from the exit doors to a public way. No exterior lighting is shown in these plans, therefore please show that the exception to this Code Section is satisfied. |
10/07/2020 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Please respond to all review comments in writing. 2. South elevations 2/A5.1 shows an evaporative cooler and a wall louver being removed from the existing shop building. Please confirm whether or not this louver must be replaced in the existing building elsewhere, presumably for proper functioning of the evaporative coolers. 3. The new addition requires ventilation per 2018 IMC 401.2. Either show that the proposed openings in exterior walls satisfy the natural ventilation requirements per Section 402 of the 2018 IMC, or provide mechanical ventilation per Section 403. |
10/07/2020 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Please respond to all review comments in writing. 2. Section 0721 Building Insulation, item G, on sheet G3.1 indicates R-19 batt (cavity) insulation for exterior walls. However, details on sheet A10.1 show 2 ½" of rigid insulation only for exterior walls. Prescriptively, Table C402.1.3 of the 2018 IECC requires R-13 cavity insulation plus R-6.5 continuous insulation. Please coordinate the information in these drawings. 3. That note on sheet G3.1 also specifies R-30 batt insulation for the roof. However, details on sheet A10.1 show what appears to be rigid insulation with a note to match the existing shop building roofing system. Please coordinate the information in the Specification with the building details. 4. Per Deferred Submittals note on sheet S0.1, please have the structural engineer review the metal building drawings and calculations and place his review seal on them. 5. Submit Varco Pruden metal building structural calculations that are not secured so that the City of Tucson approval stamp can be applied and file flattened. |
10/07/2020 | PIMA COUNTY | WATER | REVIEW | Passed | |
10/07/2020 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Please respond to all review comments in writing. 2. Provide roof drainage gutter and drain calculations per 2018 IPC Chapter 11. |
12/02/2020 | JGARCIA1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/02/2020 | JGARCIA1 | APPROVAL SHELF | Completed |
12/02/2020 | JGARCIA1 | OUT TO CUSTOMER | Completed |
12/02/2020 | JGARCIA1 | REJECT SHELF | Completed |