Permit Number: T20CM05814
Parcel: 112010860

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM05814
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide a plan set in a single PDF file for compliance review. Show the code reference: 2018 IRC. Show the north arrow and street address on the site plan.
Change the center beams to 4x8 rather than 4x6. The end beams may be 4x6 which only carry 1/4 of the roof load.

See sample plan at the web site: https://www.tucsonaz.gov/pdsd/residential-permits (Porch Sample)
07/02/2021 SAMUEL ROGERS ZONING REVIEW Reqs Change FROM: Samuel Rogers
PDSD Zoning Review Section

PROJECT: T20CM05814 (Project Number)
Residential Carport (Project Type) (4th Review)
3935 N Country Club Rd. St: #44

TRANSMITTAL DATE: 07/02/2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: The site plan does not meet minimum site plan/plot plan standards as illustrated online here: www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf

Please add required elements to the plan such as: north arrow, property owner name, lot coverage calculations, adjacent zoning, etc.


02. COMMENT: Detached accessory structures (such as a detached carport,) are not allowed in the front yard. Show that the carport is attached by a minimum 5’ connection and has a 20 lbs. live load.


03. COMMENT: Clearly identify the lots location with an accurate address and parcel number and add information to the site plan


04. COMMENT: It is unclear whether the proposed carport is located on private property, or if it proposed on commonly owned property of the homeowners association. Provide additional information with next submittal


If you have any questions about this transmittal, Contact Samuel Rogers at Samuel.Rogers@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans