Permit Number: T20CM05794
Parcel: 11454002A

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM05794
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2020 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL
FROM: Steve Shields
Site Section Manager

PROJECT:
T20CM05794
8720 E Bears Path Rd
New Shop, Outdoor Kitchen and Addition to Guest House

TRANSMITTAL: September 2, 2020
COMMENTS: The following comments are for the purpose of applying for a variance before the Board of Adjustment (UDC Section 3.10.1).

This site is located in the RX-1 zone (UDC 4.7.6). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-1). See Use-Specific Standards 4.9.7.B.6, .8, & .9.

1. Based on permit T08CM02841 the existing detached living quarters has been converted to a 2nd dwelling unit. Per UDC Table 6.3-1.A: DIMENSIONAL STANDARDS FOR THE RH, SR, SH, RX-1, & RX-2 ZONES, RX-1 Zone, only one (1) dwelling unit is allowed on this parcel, a board of Adjustment for Variance is required for the second dwelling unit.

2. Per UDC Article 6.6.3.C Accessory structures shall not exceed 12 feet in height, unless attached to a principal structure. Per UDC Article 6.4.4.A Building height is the vertical distance measured from the design grade elevation to the middle (between the eave and ridge) of the highest gable of a pitched or hipped roof. That said the proposed shop building exceeds the allowed 12' height. Correct building height was not provided.

3. The minimum setback is twenty feet (20) facing each interior property line (Table 6.3-1.A).Proposed perimeter yard setback from the addition to the guest house and the shop to the west property line is 17'-0". Proposed perimeter yard setback from the proposed shop to the south property line is 15'-0"

If the Board of Adjustment is approved provide a note on the plot plan stating the case number, date of approval, what was modified and if applicable conditions of approval.
09/02/2020 SSHIELD1 ENGINEERING REVIEW Passed
09/02/2020 SSHIELD1 NPPO REVIEW Passed
10/19/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed