Permit Number: T20CM05774
Parcel: 12711133A

Address:
815 N SONOITA AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM05774
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2020 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Steve Shields
Site Section Manager

PROJECT: T20CM05774
815 N Sonoita Ave
RV Shelter

TRANSMITTAL: Date: October 28, 2020

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.


1. Provide fully dimensioned building elevations for the proposed RV Cover so that perimeter yard setbacks can be verified. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line, UDC Table 6.3-2.A. It appears that the proposed RV Cover encroaches into the setback to the south and west property line. Either move the proposed RV Cover to meet perimeter yard setbacks or provide a neighbor setback waive on the plan. If you elect to use the setback waiver provide the following statement on the plot PLAN for both the owner to the south and west and have the owners of the properties sign and date:
“My Name is and I am the owner of the property located at . I have reviewed the site plan and I have no objection to structure being located or constructed from the property line as depicted on the site plan.

2. Per Unified Development Code (UDC) Article 6.6.3.C Accessory structures shall not exceed 12 feet in height, unless attached to a principal structure. Per UDC Article 6.4.4.A building height is the vertical distance measured from the design grade elevation to the middle (between the eave and ridge) of the highest gable of a pitched roof. Based on the VersaTube User Guide this structure exceeds the allowed height for an accessory structure. A Board of Adjustment for Variance is required. Variance requirements can be found at: https://www.tucsonaz.gov/files/pdsd/codes/Zoning_Administration_Application_BA_fillable.pdf

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
10/28/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change PROVIDE STRUCTURE PLANS WITH AN ARIZONA ENGINEER'S STAMP FOR VERIFYING STRUCTURE INTEGRITY FOR LOCAL WIND LOADS.