Permit Number: T20CM05741
Parcel: 107081130

Address:
768 W TIPTON DR

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM05741
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2020 ANDREW CONNOR NPPO REVIEW Passed
10/23/2020 LOREN MAKUS ENGINEERING REVIEW Passed
10/26/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM05741
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

FLOOR PLANS:

1. Show the functional name of each adjacent room, R106.1.1. Show any alterations to the existing kitchen. A single family dwelling may only have one kitchen.

PLUMBING PLANS:

1. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). A 1” pipe is required between the meter and first branch tee.

ELECTRICAL PLANS:

1. Show or notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.
2. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style, or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Adjustable security light fixtures are unshielded, not FCO.

If you have any questions, please contact:
Ken Van Karsen
(520) 791-5550
City of Tucson Residential Plan Review
10/28/2020 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell. Planner
T20CM05741
768 W Tipton Dr.
Residential Addition
October 28, 2020

The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.

Please resubmit the plans addressing the following comments:

1. Provide a detailed site plan following the criteria in this link: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf

a) Ensure lot coverage calculations are provided, including all structures and vehicular use areas on the property.

2. Provide a detailed floor plan of all of the structures on the property, including the existing buildings. If the number of bedrooms in the R-1 zone exceeds five, additional parking will be required and shown on the plan to adhere to zoning regulations. For a single family dwelling in the R-1 zone with five bedrooms, three parking spaces are required. For every bedroom over five, one additional space is required for each bedroom. For a review on parking standards, please submit the full floor plan.

If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov