Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM05701
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/07/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 06/07/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/07/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not resolved. The architectural and plumbing plans show a free-standing point-of-use water dispenser with no cup dispenser; the plumbing fixture schedule, however, specifies a wall-mounted bottle filler. Coordinate the type of appliance that will be used and provide the required cup dispenser. [Second comment: Comment not addressed. The engineer appears to have responded to comments that were not made. This comment should actually be addressed by the architect.] [initial comment: The use of a point-of-use water dispenser in lieu of a drinking fountain requires the installation of a listed and labeled dispenser along with a permanently mounted disposable cup dispenser. The cup dispenser shall be located adjacent to the water dispenser with the dispensing end between 34” and 48” above the finished floor.] |