Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM05701
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/20/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed. The engineer appears to have responded to comments that were not made. This comment should actually be addressed by the architect. [initial comment: Demonstrate energy code compliance for the alteration to the building envelope using calculations based on the current code. Reference: Sections C503.1 and C503.3, International Energy Conservation Code 2018.] |
| 05/20/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed. The engineer appears to have responded to comments that were not made. This comment should actually be addressed by the architect. [initial comment: The use of a point-of-use water dispenser in lieu of a drinking fountain requires the installation of a listed and labeled dispenser along with a permanently mounted disposable cup dispenser. The cup dispenser shall be located adjacent to the water dispenser with the dispensing end between 34” and 48” above the finished floor.] |
| 05/20/2021 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Comment not addressed. [Initial comment: Provide the size and serial number of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.] |
| 06/03/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |