Permit Number: T20CM05682
Parcel: 125050730

Address:
2426 E 4TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM05682
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2020 ANDREW CONNOR NPPO REVIEW Passed
09/01/2020 JOHN VAN WINKLE ENGINEERING REVIEW Passed
09/10/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM05682
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

ELECTRICAL PLANS:

1. Smoke alarms are required within sleeping rooms, R314.3.3. Add to plans.
2. Show all receptacle outlets located outdoors, at bathrooms, kitchen countertops, unfinished basements, garages or carports at grade level and within 6’ of a wet bar or sink with ground fault circuit interrupting protection, E3902.
3. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, ceiling R=38 and framed walls R=13. Mass wall requirement is R=4 when 50% of insulation is exterior and R=6 when applied interior, N1102.1. Show a means of achieving the prescriptive values at each assembly on the plans.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
09/22/2020 ALEXANDRA HINES ZONING REVIEW Approved