Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T20CM05677
Parcel: 11010283A

Address:
3170 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM05677
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2020 STEVE SHIELDS ZONING REVIEW Approved
09/01/2020 SSHIELD1 ENGINEERING REVIEW Passed
09/03/2020 JPEELDA1 FIRE REVIEW Approved
09/29/2020 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Completed
09/29/2020 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Completed
09/29/2020 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change 1. Please respond to each review comment in writing.
2. The demolition plan on sheet D-1.0 shows a new 1-hour wall in what was a hallway leading to an exit. This seems to indicate that this 1,952 SF floor area was part of the adjacent tenant space and is being made into a separate lease area. As part of the Code review provide an analysis of the adjacent tenant space showing that its exiting, exit access travel distance, dead ends, corridor fire rating (since the building is not fire-sprinkled per the Code Review), and plumbing fixture amounts comply with the 2018 IBC when a means of egress and two toilet rooms are eliminated. Ref. 2018 IBC 107.2.1, Table 1017.2, Table 1020.1, 1020.4.
3. Suite 101 is shown in the project address on sheet A0.0. Please confirm that this address is for this space only and not for this space and adjacent floor area necessitating Pima County Addressing to create an additional suite number for 3170 N Swan Rd. Contact Pima County Addressing if so.
4. Either provide an analysis of the entire building showing that it is non-separated use, or show that the (new) demising wall between this tenant area and the adjacent tenant area is 1-hour fire-rated for its entire length. Ref. 2018 IBC Table 506.2, 508.3, 508.4, Table 508.4.
5. At detail A/A-3.0, New Front Entry Door Elevation, please add the energy performance requirements applicable to this glazed unit (door 100) shown in 2018 IECC Table C402.4 for Climate Zone 2.
6. Submit a completed City of Tucson Special Inspections Certificate.
09/29/2020 PIMA COUNTY WATER REVIEW Completed
09/29/2020 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Completed
09/29/2020 PC_CANDERS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/26/2020 VFLORES1 APPROVAL SHELF Completed
10/26/2020 VFLORES1 OUT TO CUSTOMER Completed
10/26/2020 VFLORES1 REJECT SHELF Completed