Permit Number: T20CM05670
Parcel: 14043013E

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM05670
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2020 JPEELDA1 FIRE REVIEW Approved
09/08/2020 EHAMBLI1 OIP REVIEW Passed
09/08/2020 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T20CM05670

1) Provide a seperate Development Package for this submittal. Submittal to include an update to the Master Developed Area Detention/Retention requirments for the watershed in which this project is located to verify that no detention/retention triggers are being met
2) Reference City of Tucson Administrative Manual section 2-06
3) Once the development package has been approved, Engineering can approve the building plans

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
09/08/2020 ELISA HAMBLIN ZONING REVIEW Reqs Change T20CM05670
All City-owned properties are subject to archaeological review per City administrative directives. Please contact Jodie Brown at Jodie.Brown@tucsonaz.gov to determine if additional documentation is required for this site. Provide letter or email from Jodie with next plan submittal.
See Engineering comments for other applicable site requirements.
Elisa Hamblin, AICP
Principal Planner
Elisa.Hamblin@tucsonaz.gov
09/24/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/24/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet CS1.101; General Structural Notes (Geotechnical): This note indicates a geotechnical report was not developed for this project. However, a geotechnical report is included in the drawings. Please coordinate.
2. Sheet SS0.001; General Structural Notes (Foundations): Please indicate the Geotechnical Report Number and recommendations in this note.
3. Sheet SS1.002 (Roof Framing Plan); Detail 206/SS5.201: Detail 206/SS5.201 was not located on the Roof Framing Plan on Sheet SS1.002. Please verify.
4. General: Please provide a Special Inspections Certificate with Parts A and B completed.
5. General: Please provide written responses to all review comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/06/2020 PCAMARE1 OUT TO CUSTOMER Completed