Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T20CM05639
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/31/2020 | ANDREW CONNOR | NPPO | REVIEW | Passed | |
| 09/01/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
| 09/03/2020 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. PROVIDE A COMPLETE PLAN SET showing all proposed alterations and additions. Place each plan sheet into a single PDF file. Use the Residential Plan Requirements & Checklist at https://www.tucsonaz.gov/pdsd/residential-permits Sample plans are available on request. PDSD-Residential@tucsonaz.gov SITE PLAN: Provide a site plan showing all buildings, R106.1.1. Show setbacks to property lines and location of utility lines to the building. FLOOR PLAN: Provide a floor plan showing each room with labeled function. Scale ¼” = 1’. Label the function of each room. Show door and window size and location. SECTIONS - DETAILS: Provide structural details showing code compliant materials and fasteners from the foundation to the roof covering of new exterior walls. Include the foundation dimensions and floor separation from grade. Show rating of insulation. PLUMBING PLANS: Provide piping details showing code compliant materials and sizes. MECHANICAL PLANS: Provide equipment details showing code compliant components, locations and sizes. ELECTRICAL PLANS: Provide wiring details showing code compliant devices and sizes. Show circuit size with receptacles at all walls and lighting control at each doorway. Include a panel schedule. OUTDOOR LIGHTING CODE: Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. INTERNATIONAL ENERGY CONSERVATION CODE: Provide insulation details showing code compliant placement of materials and ratings, N1101. If you have any questions, please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
| 09/14/2020 | PC_TGUTHEI1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/14/2020 | PC_TGUTHEI1 | OUT TO CUSTOMER | Passed |
| 09/14/2020 | PC_TGUTHEI1 | REJECT SHELF | Passed |
| 09/14/2020 | PC_TGUTHEI1 | APPROVAL SHELF | Passed |