Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/05/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/05/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
10/05/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
10/05/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Detail 2/P-2 calls for the new water heater safety pan drain and the temperature and pressure relief to terminate over a non-existent mop sink. Clarify the termination of these pipes. Reference: Section 504, IPC 2018. |
10/15/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide compliance with the 2018 IECC for the lighting. Plan sheet E-4 references 2017 IECC. The energy in watts per sq ft in not correct, see table C405.3.2(2), 2018 IECC. 2. Designate a branch circuit number on the power plan for the receptacles. NEC 408.4. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |