Permit Number: T20CM05621
Parcel: 130050980

Address:
2042 S AMALIA AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM05621
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2020 ANDREW CONNOR NPPO REVIEW Passed
09/01/2020 LOREN MAKUS ENGINEERING REVIEW Passed
09/02/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM05621
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

Consolidate pages of construction plans into a single .PDF file as prescribed at the PDSD web site. https://www.tucsonaz.gov/pdsd/online-permits

PLUMBING PLANS:

1. Show an individual water heater for each building, P2801.1.
2. When specifying a gray drain line with a (drainage and waste listed) diverter valve, show a complete collection and discharge system consistent with P3009 for Recycling Systems with backflow and overflow provision.
3. Specify a listed diverter valve approved for sewer discharge. The Jandy Valve is not compliant for building sewer drainage.

MECHANICAL PLANS:

1. Show bathroom (without a window) exhaust fan locations with minimum 50 CFM rating and duct to the exterior, R303.3 and M1505.
2. Show a supply duct rather than return duct in the bathroom, M1602.2.4.

ELECTRICAL PLANS:

1. Show service panels on a Riser Diagram for each building. A feeder is required for serving the existing building, NEC 225.30 and E3403.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review