Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2021 STEVE SHIELDS ZONING REVIEW Approved Unitl DP16-0156 revision has been approved these plans cannot be approved.
01/13/2021 STEVE SHIELDS ZONING REVIEW Approved DP16-0156 now approved.
10/12/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a complete Electrical Plan including wiring methods in compliance with 2017 NEC art 514 for classified areas.
2. Plans are to be designed and sealed by an Electrical Engineer registered in the State of Arizona.
Ref: ARS sec R4-30-302.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
10/22/2020 JPEELDA1 FIRE REVIEW Reqs Change Please provide proper ID ( NFPA 704 diamond, no smoking sign, Propane sign etc)
Estop location on drawings showing 20-100 feet from tank
Provide and show a manual propane shutt off
An operational permit from TFD for LP gas shall be obtained and approved