Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet E-002. Specifications note 1.0A. Revise reference to NEC to the current 2017 edition.
2. Ref; Plan Sheet E-601. Identify new panel 'A' on the line diagram.
3. Ref; Plan Sheet EP 101.
(a) Detail 'C' Note states to "Refer to sheet EP 101 for additional information". Where is this information?
(b) General Note 'G,H, and I, states," To replace panel 'TML' with new 100 panel". Provide detailed information for this new 100 amp panel.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code.