Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2020 JPEELDA1 FIRE REVIEW Approved
08/20/2020 DTRAMME1 ENGINEERING REVIEW Passed
08/28/2020 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/28/2020 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL – COMMERCIAL
Reviewer: Chris Anderson
1. Please respond to all review comments in writing.
2. The Mechanical COMcheck states for the four 236 kBtu/h RTU’s that “no minimum efficiency requirement applies.” Please provide Code reference to support this.
3. Please provide heating and cooling load calculations summary sheet(s) for each mechanical equipment to justify the capacities for all heating and cooling equipment shown in the Roof Top Unit Schedule on sheet M1.1. Load calculations to be performed based on ASHRAE summer and winter ambient db design temperatures for Tucson, Arizona.
4. Please confirm that the roof top units in the Roof Top Unit Schedule were selected based on their capacities at ASHRAE summer and winter ambient db design temperatures for Tucson, Arizona. Provide those design temperatures in a note at the schedule.
5. In the Roof Top Schedule notes provide specification notes for heating and cooling equipment controls showing required deadband, setbacks, and automatic start per 2018 IECC Section C403.
08/28/2020 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL – COMMERCIAL
1. Light fixture D on the Light Fixture Schedule has a 4000 K color temperature rating. Per the 2012 City of Tucson/Pima County Outdoor Lighting Code 402.1 the maximum color temperature rating allowed for exterior lights is 3500 K.
08/28/2020 JGARCIA1 WATER REVIEW Passed
08/28/2020 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change Reviewer: Chris Anderson
August 26, 2020
BUILDING – COMMERCIAL
1. Please respond to all review comments in writing.
2. The exterior elevations, sheets A-3 and A-4 refer to new storefront and entrances being by Landlord. Either indicate on these elevations specifying requirements, or add notes to each “By Separate Permit.” If these drawings will be used for supplying vendor, show which glass panes must be safety glazing per 2018 Section 2406. Also indicate, either at the elevations or in Division 8 - Section 08400 Aluminum Storefront of the Project Specifications, that for fixed fenestration the maximum U-factor is 0.50, for operable fenestration the maximum U-factor is 0.65, and for entrance doors the maximum U-factor is 0.83. You must add the maximum solar heat gain coefficients (SHGC) to the note per Table C402.4 of the 2018 IECC based on window and door orientation and shading.
3. Provide a valuation of work to be performed.
08/28/2020 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLUMBING – COMMERCIAL
Reviewer: Chris Anderson
1. Please respond to all review comments in writing.
2. Please confirm that the faucet for lavatories L-1 dispense no more than .25 gallon per metering cycle. Ref. City of Tucson amendment to the 2018 IPC 419.6.
3. Provide a plan showing condensate lines and approved termination for all heating and cooling equipment. Ref. 2018 IPC Section 314 and City of Tucson amendment to 314.2.1.
09/09/2020 SAMUEL ROGERS ZONING REVIEW Approved