Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM05338
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/19/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 08/20/2020 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
| 08/28/2020 | JGARCIA1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/28/2020 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | MECHANICAL – COMMERCIAL Reviewer: Chris Anderson 1. Please respond to all review comments in writing. 2. The Mechanical COMcheck states for the four 236 kBtu/h RTU’s that “no minimum efficiency requirement applies.” Please provide Code reference to support this. 3. Please provide heating and cooling load calculations summary sheet(s) for each mechanical equipment to justify the capacities for all heating and cooling equipment shown in the Roof Top Unit Schedule on sheet M1.1. Load calculations to be performed based on ASHRAE summer and winter ambient db design temperatures for Tucson, Arizona. 4. Please confirm that the roof top units in the Roof Top Unit Schedule were selected based on their capacities at ASHRAE summer and winter ambient db design temperatures for Tucson, Arizona. Provide those design temperatures in a note at the schedule. 5. In the Roof Top Schedule notes provide specification notes for heating and cooling equipment controls showing required deadband, setbacks, and automatic start per 2018 IECC Section C403. |
| 08/28/2020 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | ELECTRICAL – COMMERCIAL 1. Light fixture D on the Light Fixture Schedule has a 4000 K color temperature rating. Per the 2012 City of Tucson/Pima County Outdoor Lighting Code 402.1 the maximum color temperature rating allowed for exterior lights is 3500 K. |
| 08/28/2020 | JGARCIA1 | WATER | REVIEW | Passed | |
| 08/28/2020 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Reviewer: Chris Anderson August 26, 2020 BUILDING – COMMERCIAL 1. Please respond to all review comments in writing. 2. The exterior elevations, sheets A-3 and A-4 refer to new storefront and entrances being by Landlord. Either indicate on these elevations specifying requirements, or add notes to each “By Separate Permit.” If these drawings will be used for supplying vendor, show which glass panes must be safety glazing per 2018 Section 2406. Also indicate, either at the elevations or in Division 8 - Section 08400 Aluminum Storefront of the Project Specifications, that for fixed fenestration the maximum U-factor is 0.50, for operable fenestration the maximum U-factor is 0.65, and for entrance doors the maximum U-factor is 0.83. You must add the maximum solar heat gain coefficients (SHGC) to the note per Table C402.4 of the 2018 IECC based on window and door orientation and shading. 3. Provide a valuation of work to be performed. |
| 08/28/2020 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | PLUMBING – COMMERCIAL Reviewer: Chris Anderson 1. Please respond to all review comments in writing. 2. Please confirm that the faucet for lavatories L-1 dispense no more than .25 gallon per metering cycle. Ref. City of Tucson amendment to the 2018 IPC 419.6. 3. Provide a plan showing condensate lines and approved termination for all heating and cooling equipment. Ref. 2018 IPC Section 314 and City of Tucson amendment to 314.2.1. |
| 09/09/2020 | SAMUEL ROGERS | ZONING | REVIEW | Approved |