Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM05320
Parcel: 117144050

Address:
633 S MEYER AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM05320
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2020 ANDREW CONNOR NPPO REVIEW Passed
08/18/2020 LOREN MAKUS ENGINEERING REVIEW Passed
08/18/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM05320
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration

GENERAL COMMENTS:

1. Provide a complete set of construction plans detailing alterations or improvements for achieving code compliance with the 2018 IRC, R105.
2. Provide a signed Confirmation of Notice of Demolition form if removing a building roof or walls before obtaining the building permit, R104.

FLOOR PLANS:

1. Clarify the new and proposed rooms, R106.1.1.

STRUCTURAL PLANS:

1. Provide an engineer’s calculation, design and seal for masonry partition and screen walls exceeding 7’ in height above grade on either side. Sheet A3.01 shows 8’-6” height.

PLUMBING PLANS:

1. Show any plumbing changes in compliance with the code recognized by the City of Tucson, 2018 IRC.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation, or controlled exhaust with a calculated airflow rate, R303.4; N1103.6 & M1505.4. Show the system and appropriate flow rate setting on the plans. A two or three bedroom dwelling of 1501 – 3000 SF requires a 60 CFM continuous setting.
2. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Notate if the mechanical system calculations may be provided by deferred submittal.

ELECTRICAL PLANS:

1. Show electrical changes in compliance with the code recognized by the City of Tucson, 2018 IRC.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
09/01/2020 ALEXANDRA HINES ZONING REVIEW Reqs Change 1. Provide director decision letter from historic review (UDC 5.8.8) in resubmittal. Zoning review of building permit, T20CM05320, not approvable until historic review, T20SA00234, approved. This site is located in the HC-3 zone (UDC 4.7.22). A single-family residence (SFR) is a permitted use in this zone (Table 4.8.6). No Use-Specific Standards. The minimum setback is zero (0) feet facing each interior property line (Table 6.3-4.A).
2. Demonstrate compliance with conditions, if any, from director decision letter on site plan or elevation.
3. Provide interior plan of existing adobe dwelling on site plan.
4. Complete or withdraw interior demolition permit, T18CM07358, by obtaining approved inspection, so the permit can go to Final status. This informs the comment above.
5. Provide density calculation on site plan. Provide general note. Does the lot have 1 unit with accessory sleeping quarters or 2 units? Both are permitted in the HC-3 zone. See https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf for calculation reference.
6. Complete demolition permit, T18BU00181, by obtaining approved inspection, so the permit can go to Final status. This informs staff since the structures show on the aerial.

Alexandra Hines
alexandra.hines@tucsonaz.gov