Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM05287
Parcel: 113052460

Address:
2028 E PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM05287
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2020 JPEELDA1 FIRE REVIEW Approved
08/26/2020 DTRAMME1 ENGINEERING REVIEW Passed
09/08/2020 STEVE SHIELDS ZONING REVIEW Approved
09/17/2020 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Completed 1. Demonstrate energy code compliance for the alterations to the building envelope using calculations based on the current code (e.g. installation of solatubes and window replacement). Reference: Sections C103.2, C303, C503.1, and C503.3, International Energy Conservation Code 2018.
2. Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, 504.4 and, 504.6, IMC 2018.
09/17/2020 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Completed
09/17/2020 PIMA COUNTY WATER REVIEW Completed Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
09/17/2020 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Completed
09/17/2020 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Completed 1. Provide plumbing plans for the new work (e.g. new clothes washer, relocated sinks, etc.) including water isometrics and waste and vent isometrics. Reference: Section 107.2.1, IBC 2018.
2. Check the floor plan keynotes for correctness (e.g. #16 labels a lavatory as an existing column, see also 11, 12, 14, 15, 17, 18, 19, 20, 21, and 22). Reference: Section 107.2.1, IBC 2018.
3. Explain why a service sink and a drinking fountain are not required for a business occupancy of 22 persons. Reference: Footnote c, Table 2902.1, IBC 2018 and Section 410.2, IPC 2018.
4. Verify that the new water heater has a thermal expansion tank. Reference: Section 607.3, IPC 2018.
09/17/2020 CTREVIL1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed