Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM05233
Parcel: 11620636B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM05233
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/12/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The new hood requires an additional 480 CFM of makeup air. Operable windows and doors can be used as the sole source of makeup air only if they are controlled to automatically open when the hood is operating and the location of the openings comply with Section 401.4, IMC 2018. Reference: Section 508.1, IMC 2018.
08/12/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The plumbing plan indicates that the grease trap is existing but the architectural plans call out the installation of a new grease trap. Which version is correct? Reference: Section 107.2.1, IBC 2018.
08/12/2020 LOREN MAKUS ENGINEERING REVIEW Passed
08/12/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/12/2020 ROBERT SHERRY WATER REVIEW Completed
08/12/2020 JPEELDA1 FIRE REVIEW Approved
08/18/2020 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
08/18/2020 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/25/2020 VLEON1 APPROVAL SHELF Completed
08/25/2020 VLEON1 OUT TO CUSTOMER Completed
08/25/2020 VLEON1 REJECT SHELF Completed