Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM05233
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/12/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/12/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The new hood requires an additional 480 CFM of makeup air. Operable windows and doors can be used as the sole source of makeup air only if they are controlled to automatically open when the hood is operating and the location of the openings comply with Section 401.4, IMC 2018. Reference: Section 508.1, IMC 2018. |
08/12/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The plumbing plan indicates that the grease trap is existing but the architectural plans call out the installation of a new grease trap. Which version is correct? Reference: Section 107.2.1, IBC 2018. |
08/12/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
08/12/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/12/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/12/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
08/18/2020 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
08/18/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/25/2020 | VLEON1 | APPROVAL SHELF | Completed |
08/25/2020 | VLEON1 | OUT TO CUSTOMER | Completed |
08/25/2020 | VLEON1 | REJECT SHELF | Completed |