Permit Number: T20CM05210
Parcel: 119215970

Address:
1730 W AJO WY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM05210
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2020 ROBERT SHERRY PLUMBING-RESIDENTIAL REVIEW Reqs Change 1. Revise the plumbing fixture description to include the dispensing requirements for the faucet (i.e. maximum gallons per metering cycle, minimum time per cycle). [Initial comment: Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.]
2. The maximum distance from the hot water source to the stop valve for the lavatory is 24" for ½" pipe or 6" for ¾" pipe. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.]
11/17/2020 ROBERT SHERRY MECHANICAL-RESIDENTIAL REVIEW Completed
11/18/2020 DSANTAC2 ELECTRICAL-RESIDENTIAL REVIEW Approved