Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM05210
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/17/2020 | ROBERT SHERRY | PLUMBING-RESIDENTIAL | REVIEW | Reqs Change | 1. Revise the plumbing fixture description to include the dispensing requirements for the faucet (i.e. maximum gallons per metering cycle, minimum time per cycle). [Initial comment: Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.] 2. The maximum distance from the hot water source to the stop valve for the lavatory is 24" for ½" pipe or 6" for ¾" pipe. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.] |
| 11/17/2020 | ROBERT SHERRY | MECHANICAL-RESIDENTIAL | REVIEW | Completed | |
| 11/18/2020 | DSANTAC2 | ELECTRICAL-RESIDENTIAL | REVIEW | Approved |