Permit Number: T20CM05210
Parcel: 119215970

Address:
1730 W AJO WY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM05210
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1, 504, 606.1, 607.2, and 607.3, IPC 2018.
3. The vent configuration of sanitary stack detail does not comply with the requirements of the horizontal wet vent (Section 912, IPC 2018), circuit vent (Section 914, IPC 2018), or the combination waste and vent system (Section 915, IPC 2018). Show that each trap and trapped fixture has been vented in accordance with one of the methods shown in the IPC. Reference: Section 901.2.1, IPC 2018.
4. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
11/04/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change If space is provided for the installation of a clothes dryer now or in the future, the installation of an exhaust duct will be required. Reference: Section 504.8.6, IMC 2018.
11/09/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Revise the lighting energy Comcheck to the current adopted 2018 IECC.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.