Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM05210
Parcel: 119215970

Address:
1730 W AJO WY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM05210
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/23/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Comment not addressed. [Initial comment: Provide construction documents that are complete and clearly indicate the extent of the proposed mechanical work. Reference: Section 107.2.1, IBC 2018.]
09/23/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not addressed. [Initial comment: Provide construction documents that are complete and clearly indicate the extent of the proposed plumbing work. Reference: Section 107.2.1, IBC 2018.]
10/07/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide complete electrical floor plans. Include;
(a) Designated branch circuits and panel for all power devices and lighting. NEC 408.4.
(b) Complete panel schedule including load calculations for increased load as the result of the proposed electrical installations.
(c) Clearly indicate what is new and what is existing on the plans.
(d) Provide compliance with the 2018 IECC for the lighting.
Ref; 2018 IBC 107.2.1, 2017 NEC.