Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM05210
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/11/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
08/11/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide construction documents that are complete and clearly indicate the extent of the proposed mechanical work. Reference: Section 107.2.1, IBC 2018 |
08/11/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide construction documents that are complete and clearly indicate the extent of the proposed plumbing work. Reference: Section 107.2.1, IBC 2018. |
08/11/2020 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
08/11/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/12/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A0.3; Accessibility Requirements: Per the 2009 ICC/ANSI Section 602.4, the drinking fountain spout outlet heights shall be provided for wheelchair bound occupants (36" maximum height above finish floor), and for standing occupants (38" minimum to 43" maximum height above finish floor). Please revise that note. The City of Tucson allows the drinking fountain to be a high/low, or a single point of use dispenser with cups at an accessible height. 2. Sheets A1.0.1, A1.1.1, A1.1.2, and A1.1.3; Plans: Please provide a north arrow on all plans. 3. Sheet A1.1.1; Keyed Notes: Note 3 is not listed in the Keyed Notes, but is indicated on the Floor Plan (at the New Counter). Please verify. 4. Sheet A1.1.1; Floor Plan: At the New Counter, a Keyed Note 5 is indicated. Please verify that note is correct. 5. Sheet A1.1.1; Keyed Notes: Notes 6, 8, 9, 15, 16, 17, 18, 22, and 24 were not located on the plan. Please verify. 6. Sheet A1.1.1; Floor Plan: Next to the New Toilet, a Keyed Note 1 is indicated. Please verify that note is correct. 7. Sheet A1.1.1; Floor Plan: An elevation at the New Counter references 3/A7.0. Please revise that reference, and indicate the elevation on the Floor Plan. 8. Sheet A1.1.2; Reflected Ceiling Plan: Please indicate the exit signs on this plan. 9. Sheet A2.0; Door Detail 1 (Head): Please indicate the metal stud kickers size, gauge, and spacing. In addition, indicate how the kickers connect to the roof structure above, and the size and quantity of screws in that connection. 10. Sheet A5.0; Water Heater Support Detail 4: Please indicate the gauge of the metal studs supporting the water heater, and how those studs connect to the wall. 11. General: Please provide written responses to all review comments. |
08/12/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/18/2020 | JGARCIA1 | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Provide construction documents that are complete and clearly indicate the extent of the proposed electrical work. Reference: Section 107.2.1, IBC 2018. |
08/19/2020 | JPEELDA1 | FIRE | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/11/2020 | PC_TGUTHEI1 | OUT TO CUSTOMER | Passed |
09/11/2020 | PC_TGUTHEI1 | REJECT SHELF | Passed |
09/11/2020 | PC_TGUTHEI1 | APPROVAL SHELF | Passed |