Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T20CM05201
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/20/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: Steve Shields Site Section Manager PROJECT: T20CM05201 720 N Olsen Ave Residential remodel and addition TRANSMITTAL: August 20, 2020 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). Based on a wall height of less than 9'-0" the required perimeter yard setback from the expansion of the carport to the south property line is 6'-0", proposed is 2'-7". The maximum height of a wall or fence within a perimeter yard shall be six (6) feet (UDC Section 6.6.2.I). Proposed height of the site wall along the south property line is 7'-0". Design Development Option required for both items. |
| 08/20/2020 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 08/20/2020 | ANDREW CONNOR | NPPO | REVIEW | Passed | |
| 09/17/2020 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Completed |