Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/10/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the scope of work. Drawing A1 through A3 do not appear to relate to the submitted structural drawings.
2. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304
08/10/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the scope of work. Drawing A1 through A3 do not appear to relate to the submitted structural drawings.
2. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304
08/10/2020 LOREN MAKUS ENGINEERING REVIEW Passed
08/10/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheets A1, A2, and A3: Please provide construction documents prepared by a registered design professional per the IBC Section 107.1.
2. Sheet A1; Floor Plan: Please indicate the new mezzanine on this floor plan.
3. Sheet A2; Plans: Please identify each plan as either Building, Electrical, or Mechanical.
4. Sheet A3; Plans: Please identify each plan as either Floor Plan or Mechanical Plan.
5. Sheet A3; Specifications (Walls): The Specifications indicate new 2x6 metal studs at 16" o.c., while the Floor Plan indicates 2x4 at 16" o.c. metal studs. Please coordinate.
6. Sheet A3; Specifications (Walls): Since these are metal studs, indicate the gauge of those studs in the Specifications (Wall Section indicates 20 gauge).
7. Sheet A3; Floor Plan: Please indicate dimensions on the Floor Plan to locate all new walls.
8. Sheet A3; Specifications: Please revise the NEC to the 2017 Edition.
9. Sheet A3; Wall Section: Please indicate on the Floor Plan where this Wall Elevation/Section is cut.
10. Sheet M1; Mezzanine Notes (Foundation): Please provide structural calculations to verify existing/new foundations are adequate to support the new mezzanine per Mezzanine Notes 2.
11. Sheet M2; Plan Layouts: Please provide north arrows on these plans.
12. Sheet M3; Floor Plan Layout: Please provide a north arrow on this plan.
13. Sheet M3; Floor Plan Layout: A note at the upper right of this plan indicates to see detail on Sheet M1 of M1 for a beam connection. Please revise the detail reference.
14. General: Please provide a Special Inspection Certificate with Parts A and B completed. This form may be found at www.tucsonaz.gov/PDSD.
15. General: Please provide a project valuation (labor + materials).
16. General: Please provide written responses to all review comments.
08/10/2020 ROBERT SHERRY WATER REVIEW Reqs Change Clarify the scope of work.
08/10/2020 JPEELDA1 FIRE REVIEW Approved
08/18/2020 JGARCIA1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the scope of work. Drawing A1 through A3 do not appear to relate to the submitted structural drawings.
2. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304
08/21/2020 STEVE SHIELDS ZONING REVIEW Approved