Permit Number: T20CM05084
Parcel: 108255470

Address:
2008 E RIVER RD

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T20CM05084
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/07/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide secondary (overflow) roof drainage for the four flat roof areas of the garage. Reference: Sections 1106.5, 1108.1, 1108.2 and 1108.3, IPC 2018.
08/07/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/07/2020 ROBERT SHERRY WATER REVIEW Passed
08/07/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheets A1.1 and A1.2: Please revise all section and detail cuts on these sheets to reference A1.1 or A1.2.
2. Sheet A1.1; Section 'A': The foundation detail on the left of this section indicates 16" minimum from finish floor to the bottom of the footing. The Soil Report recommended the bottom of footing should be a minimum of 1'-6" below finish grade. Please revise this detail.
3. Sheet A1.2; Details 1, 2, and 3: Please revise the dimensions from finish floor or finish grade to the bottom of the footing per the Soil Report recommendations.
4. Sheet A1.3: Please provide a note on this sheet indicating the total length of the fence on this project and the height of the fence.
5. Sheet A1.3: Please provide a typical detail on this sheet at a fence post and at a gate, indicating the required foundation for each.
6. General: Please provide structural calculations for the garages.
7. General: Please provide a Special Inspection Certificate with Parts A and B completed.
8. General: Please provide written responses to all review comments.
08/14/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Clearly identify the locations of the proposed improvements on the site plan. Provide reference to an approved development package or other approved site plan with these improvements.
08/19/2020 STANTEC ELECTRICAL-COMMERCIAL REVIEW Reqs Change GENERAL
1. Clearly identify panel and circuit designations for all lights, receptacles, gate operators, etc.
2. Provide a load calculation for Panel P and both the services shown that comply with 2017
NEC Art. 220.40 or 220.87

Sheet A1.1
1. Per 2012 City of Tucson /Pima COunty Outdoor Lighting Code (OLC), Sec/102.4.2 a full inventory of the lighhting is required. he calculations as presented only cover the new lights on the 10.18 - acre site. The calculations must include a; existing lighting and the new lighting being provided on the site. Provide additional information on the plans which include the following information:
a. Each exterior luminaire type with the lumens for that type, the quantity of each type and whether the luminaire is full cut-off or unshielded, and the color rendition (i.e. not to exceed 3500K)
b. The total of full cut-off and unshielded lumens for the parcel.
c. A ststement of the lighting area, the size of the permitted parcel, and the maximum allowed full cut-off and unshielded lumens.
d. A statement that special inspection is required (or is not required) per Sec. 104.2.2

Also provide lighting fixture cut sheets for each exterior fixture.
08/19/2020 JPEELDA1 FIRE REVIEW Approved
08/21/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: Placita Escondida Garage & Vehicular Gates
T20CM05084 - 1st Review)

TRANSMITTAL DATE: August 21, 2020

1. Zoning has reviewed the plan for compliance with the approved tentative plat S04-0178. Zoning acknowledges that there are garages shown on the plat but I need to know which garage this permit is for. Also there are not gates shown on the plan. Provide a copy of the approve tentative plat with your next submittal and clearly show which garage this permit is for and the location of the gates.

2. Zoning cannot approve the building plans until PDSD Commercial Plans reviewers have approved the building plans.


If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

Final Status

Task End Date Reviewer's Name Type of Review Description
10/07/2020 IMONSHI1 OUT TO CUSTOMER Completed