Permit Number: T20CM05082
Parcel: 108255470

Address:
2008 E RIVER RD

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T20CM05082
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not resolved; MH #2 is the next downstream manhole. Provide the rim elevation of MH #3. [Second comment: Comment not resolved. Provide the first-floor elevation of the clubhouse. The manhole shown on the site plan is the public manhole to which the existing private sewer collection is connected. It is not the next upstream manhole.] [Initial comment: Provide the first-floor elevation of the clubhouse and the rim elevation of the next upstream sanitary manhole of the private sewer collection system. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.]
2. The floor drain in the pool equipment room shall be connected to the sanitary drainage system. Reference: Section 301.3, IPC 2018. [Second comment: It is not clear that the floor drain is even connected to the building drain (e.g. what is the “daylight pipe through wall w/ screen”?).] [Initial comment: Clarify how the fixture drain from the floor drain in the pool equipment relates to the building drain and How the floor drain will be vented. Reference: Section 107.2.1, IBC 2018.]
05/10/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/10/2021 ROBERT SHERRY WATER REVIEW Completed
05/13/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/26/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

The electrical site plan submitted at this 3rd submittal is a copy of a plan previously sealed by an Electrical Registrant dated 2006 and shows no updated exterior lighting except the original Outdoor Lighting Calculations are X’ed out. The changes should be clearly shown, dated and stamped by the current Registrant.

Please identify the new exterior lighting on the Clubhouse electrical plan with a mark or symbol that correlates with the Exterior Lighting Calculations.

Please in include light source color temperature output of the luminaires to verify compliance with the OLC section 402.1 (3500K)

Also it was noted that the electrical line diagram does not identify all the panel feeder conductors shown. For example, the three phase panel feeders show only three conductors in the conduit, there should be five for a three phase system. 3 ungrounded, 1 grounded, 1 grounding conductor(s). (3Hots,1neutral,1ground).

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC),

City of Tucson Commercial Plan Submittal Requirements
06/07/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Placita Escondida Clubhouse
T20CM05082 – 3rd Review)

TRANSMITTAL DATE: June 7, 2021

1. This comment was not addressed. The tentative plat is a separate submittal from the building plan is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using the “Submission Type” “Site Review”. As there is no clubhouse shown on the approved tentative plat, S04-178 a revision to the tentative plat is required. As discussed previously with Andy this is a minor change and you would need to provide a copy of the approved tentative plat sheet with the area where the club house is going clouded and provide a detail of the area and revise all applicable calculations such as lot coverage. The provided email does not address the addition of a new club house.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
06/14/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change See zoning comment for need of a revision to the Tentative Plat.

Stephen Blood
(520) 837-4958