Permit Number: T20CM05069
Parcel: 114540640

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM05069
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/17/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/30/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2018 and C404.5, IECC 2018. [Initial comment: Show the location of the source of hot water for the new sinks. Reference: Section 107.2.1, IBC 2018.]
09/30/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Completed Please address the following electrical plan review comments. Also provide a written response.
1. Provide a note requiring compliance with NEC 517.13 for wiring methods in the exam rooms or patient care areas.
2. Provide Tamper Resistant Receptacles where applicable per NEC 406.12(5).
3. Provide complete compliance with the 2018 IECC for the lighting.
4. Provide a complete lighting schedule.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/17/2020 JGARCIA1 APPROVAL SHELF Completed
09/17/2020 JGARCIA1 OUT TO CUSTOMER Completed
09/17/2020 JGARCIA1 REJECT SHELF Completed