Permit Number - T20CM05038
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2020 JGARCIA1 WATER REVIEW Reqs Change 1. Tucson Water limits 1-1/2" water meters to maximum demand of 100-GPM. Your calculations indicate that the demand will be 112 GPM: provide a 2" water meter.
2. Your water pressure calculations are based on an assumed water pressure of 90 PSI but Tucson Water records show a pressure range of 37-44 PSI. Contact Tucson Water to verify the water pressure range and revise the calculations appropriately. Reference: Section 604.6, IPC 2018.
08/06/2020 JPEELDA1 FIRE REVIEW Approved
09/02/2020 SSHIELD1 ZONING HC REVIEW Passed
09/02/2020 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Section Manager

PROJECT: T20CM05038
New Office Building
4760 S Park Ave

TRANSMITTAL DATE: September 2, 2020

DUE DATE: September 2, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. The building plans have been reviewed for conformance to DP20-0122. Although the building plans appear to match what is provide on the DP Zoning cannot approve the building plans until the DP is approved and all other PDSD review agencies have approved.

2. The DP sheet provided in the building set need to be the most up to date plans.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
09/18/2020 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T20CM05038

1) Roof drains shown on sheet A8.1 do not line up with the location of sidewalk scuppers shown in the development package. Adjust plans as needed to ensure that all roof drains scupper under pedestrian circulation paths as needed

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
09/23/2020 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
09/23/2020 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Completed
09/23/2020 JGARCIA1 ADA REVIEW Completed
09/23/2020 JGARCIA1 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/23/2020 JGARCIA1 APPROVAL SHELF Completed
09/23/2020 JGARCIA1 OUT TO CUSTOMER Completed
09/23/2020 JGARCIA1 REJECT SHELF Completed