Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T20CM05013
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/17/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Per the previous Electrical plan reviewers comment # 1h, the scope of work being clarified, new comments are generated concerning the exterior lighting. (a) Only the 'A' luminaires are shown on the site plan. Where are 'B', 'C' and 'D' located? (b) The load calculation for the lighting on the panel schedule does not correlate with the total wattage of lighting installed as shown per the luminaire schedule X the number of fixtures installed. Please clarify. (c) It appears that a special inspection is required for the outdoor lighting per section 106.2.1. Please indicate this on the plan as required per section 104.2.2 of the OLC. 2. Is the "House Panel" schedule shown the same as the "Common Area Panel" shown on the Single Line Diagram? If so, Identify them accordingly. 3. Please indicate conduit, conductor sizes and types for the branch circuits. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code, (OLC). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/28/2020 | IMONSHI1 | OUT TO CUSTOMER | Completed |