Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T20CM05013
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/04/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide more information of the electrical equipment on the plan. (a) Amp ratings. (b) Voltage and Phase. (c) AIC rating. (d) Line diagram with feeder, conduit sizes and types,. (e) Grounding detail. (f) Project address. (g) The site plan shows several electric services. Identify the location of this service. (h) Please be more specific as to the scope of work. Is the exterior lighting included? Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |