Permit Number: T20CM04843
Parcel: 11941058A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM04843
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2021 JPEELDA1 FIRE REVIEW Approved Date September 24, 2020 from TW and Fred Coy:
Fire flow annalysis shows that they have 1,750 gpm for 2 hours resulting in 39 psi for residual and pass the requirements.
We still need verification that all points the house are located within 400' of the fire hydrant. Please provide plans that reflect to scale hose lay from the hydrants.