Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM04843
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/19/2021 | JPEELDA1 | FIRE | REVIEW | Approved | Date September 24, 2020 from TW and Fred Coy: Fire flow annalysis shows that they have 1,750 gpm for 2 hours resulting in 39 psi for residual and pass the requirements. We still need verification that all points the house are located within 400' of the fire hydrant. Please provide plans that reflect to scale hose lay from the hydrants. |