Permit Number: T20CM04815
Parcel: 132101650

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM04815
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: T20CM04815
1942 E Irene Vista
Garage Addition
Residential (2nd Review)

TRANSMITTAL DATE: September 3, 2020

The plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

1. The minimum setback from the proposed garage to the west property line is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing the west property line (UDC Table 6.3-2.A). Based on a wall height of 10'-0" the required perimeter yard setback from the proposed garage to the west property line is 6'-8", proposed setback is 1'-0". A Design Development Option (DDO) must be applied for and approved prior to approval of these plans. DDO application can be found at. https://www.tucsonaz.gov/files/pdsd/2019_DDO_for_Setback_and_Height_UDC.pdf
Zoning does not recommend that you apply for the DDO until comment 4 has been addressed.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
09/16/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed