Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T20CM04593
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/22/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet PV-1; City Notes: Per the IBC Section 101.2, this is a commercial project. Please remove the notations for the 2018 International Residential Code and the 2018 International Swimming Pool and Spa Code. 2. General: Please provide structural calculations for the analysis of the existing roof structure to support the new PV system. 3. General: Please provide written responses to all review comments. |
| 07/22/2020 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 07/22/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Because the multifamily building has more than two units, the project is classified as commercial. Provide plans sealed by a Registered Engineer registered in the State of Arizona. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 07/22/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | Zoning has no issues with the proposed roof mounted solar and will stamp the plans when stamped and approved by all other PDSD review agencies. |
| 07/23/2020 | JPEELDA1 | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/04/2020 | SROGERS2 | OUT TO CUSTOMER | Completed |